• Ftd301 Feeder Terminal Unit (FTU)
Ftd301 Feeder Terminal Unit (FTU)
+

Share to

Ftd301 Feeder Terminal Unit (FTU)

Key Features: ● Mainly used for monitoring and data collection of distribution lines. ● Three-remote functions: remote measurement, remote signaling, and remote control. ● Protection Functions: three-stage overcurrent protection, inverse time overcurrent protection, zero sequence current protection, reclosing,post acceleration, and closing inrush current protection. ●Intelligent distributed logic function: can quickly determine the nature of faults, achieve local fault clearance in sections, automatic fault isolation, and automatic power restoration of the non-fault section. ● Power supply function: Dual-circuit power supply switching. When AC power fails, it automatically switches to the backup power supply. ●Communication function: wireless GPRS/GSM, Ethernet interfaces, supporting MODBUS,IEC104 and other power communication protocols.

Still deciding? Get samples first,  Contact US !

View similar products

Tag list

  • Product Details
  • Key Features:
    ● Mainly used for monitoring and data collection of distribution lines.
    ● Three-remote functions: remote measurement, remote signaling, and remote control.
    ● Protection Functions: three-stage overcurrent protection, inverse time overcurrent protection, zero sequence current protection, reclosing,post acceleration, and closing inrush current protection.
    ●Intelligent distributed logic function: can quickly determine the nature of faults, achieve local fault clearance in sections, automatic fault isolation, and automatic power restoration of the non-fault section.
    ● Power supply function: Dual-circuit power supply switching. When AC power fails, it automatically switches to the backup power supply.
    ●Communication function: wireless GPRS/GSM, Ethernet interfaces, supporting MODBUS,IEC104 and other power communication protocols.

    Technical Parameters:

    No. Item Unit Technical parameters
    1 Power Supply Working Voltage V AC220V±20%
    Voltage Frequency Hz 50±5%
    2 Remote Measurement A.C. voltage Nominal Sampling Voltage V 100V
    A.C. current Nominal Sampling Current A 5A, 1A
    Rated frequency   Hz 45~55
    3 Remote Control Contact capacity   DC27V, 10A
    Input working voltage V AC220V
    Output Voltage V DC24V
    4 Power Consumption Power consumption of the whole equipment VA ≤20VA
    5 Backup Power Supply Standard: super capacitor
    Optional: external lead-acid battery, rated voltage DC24V, single battery 7Ah.

     

     

Ftd301 Feeder Terminal Unit (FTU)

Key Features: ● Mainly used for monitoring and data collection of distribution lines. ● Three-remote functions: remote measurement, remote signaling, and remote control. ● Protection Functions: three-stage overcurrent protection, inverse time overcurrent protection, zero sequence current protection, reclosing,post acceleration, and closing inrush current protection. ●Intelligent distributed logic function: can quickly determine the nature of faults, achieve local fault clearance in sections, automatic fault isolation, and automatic power restoration of the non-fault section. ● Power supply function: Dual-circuit power supply switching. When AC power fails, it automatically switches to the backup power supply. ●Communication function: wireless GPRS/GSM, Ethernet interfaces, supporting MODBUS,IEC104 and other power communication protocols.