HG11-145 GIS
Still deciding? Get samples first, Contact US !
View similar products
Tag list
- Product Details
-
HG11-145 three-phase common tank SF6 GIS,with the most advanced technology and design concepts in the world,the product adopts the modular design concept and the modular layout of standard components, which has the advantages of small floor area (with an interval width of only 0.8m), advanced technology and high reliability.HG11-145 GIS fully meets IEC 62271-203, GB7674, DL617 and other standards. With high technical parameters and stable and reliable quality.
Product Details:
HG11-145 GIS is composed of several standard functional modules, such as circuit breaker GCB, isolation-earthing combination switch (TPS), voltage transformer (VT), current transformer (CT), bushing (BSG) and busbar(BUS). These modules have the same interface form and size, and various modules can be arbitrarily combined to meet the design and layout requirements of various substations. Each module is assembled in a manner that facilitates future reconstruction and expansion, and gas-isolating insulators minimize the interaction between adjacent modules.
The flexible modular design facilitates the optimization of the design and layout of the substation, and various conditions and factors, such as main wiring, incoming line and cable routing, building size, trafficability, reserved extension and fast troubleshooting can be fully and specifically considered.
Technical ParametersNo. Item Unit Parameters 1 Rated voltage kV 145 2 Rated frequency Hz 50/60 3 Rated continuous current A 1250~3150 4 Rated short-circuit breaking current kA 40 5 Rated short circuit making current kA 108 6 Full breaking time ms ≤ 60 7 Circuit breaker switching cable charging current A 160 8 Circuit breaker switching line charging current A 50 9 Circuit breaker closing time ms ≤100 10 Circuit breaker opening time ms ≤40 11 Asynchronous circuit breaker Opening ms ≤2 Closing ms ≤3 12 Rated short-time withstand current (effective value) kA 40 13 Rated short-circuit duration s 3 14 Rated peak withstand current (effective value) kA 108 15 Rated power-frequency short-duration withstand voltage
(1min)Phase to earth,
Phase to PhasekV 275 Across the
isolating
distancekV 315 16 Rated lighting impulse withstand voltage
(Peak value)Phase to earth,
Phase to PhasekV 650 Across the
isolating
distancekV 750 17 SF6 vacuum interrupter
Gas pressure (20℃, gauge pressure)Rated pressure Mpa 0.6 Alarm pressure Mpa 0.55 Locking pressure Mpa 0.5 18 Circuit breaker electrical life E2 level 19 Rated operating sequence O-0.3s-CO-180s-CO 20 Partial discharge
(Under 1.2 times rated voltage)Wholecompartment pC 5 Insulation parts pC 3 21 Compartment weight T 1~5 22 Annual leakage rate ≤0.1%
HG11-145 GIS